Single or Double Panel? How Much Extra Radiator Output Do You Get?
Upgrading from a single-panel (Type 11) radiator to a double-panel (Type 22) radiator of the exact same height and width gives you roughly 85% to 90% more heat output—almost double the heat—while projecting only ~38 mm further from the wall.
If you want a middle ground for a tighter space, a slim double panel (Type 21 / P+) delivers roughly 45% to 50% more heat than a single panel for just ~15 mm of extra depth.
Single vs Double Panel: Exact Output and Depth (600 × 1000 mm)
Most radiator guides tell you that double panels are "warmer and thicker" without showing how much heat you gain per millimetre of wall projection. Using BS EN 442 figures for a standard UK 600 mm high × 1000 mm wide compact steel radiator:
| Specification (600 × 1000 mm) | Type 11 (K1) — Single Panel | Type 21 (P+) — Slim Double | Type 22 (K2) — Standard Double |
|---|---|---|---|
| Construction | 1 water panel, 1 fin row | 2 water panels, 1 fin row | 2 water panels, 2 fin rows |
| Radiator depth | ~62 mm | ~77 mm (+15 mm) | ~100 mm (+38 mm) |
| Total wall projection (incl. brackets) | ~86 mm | ~101 mm | ~124 mm |
| Heat output at ΔT50 (75°C / 65°C) | ~911 W (3,108 BTU/hr) | ~1,345 W (4,589 BTU/hr) | ~1,732 W (5,910 BTU/hr) |
| Extra heat vs Type 11 | Baseline | +48% heat | +90% heat |
| Heat output at ΔT30 (55°C / 45°C) | ~465 W (1,585 BTU/hr) | ~686 W (2,340 BTU/hr) | ~883 W (3,014 BTU/hr) |
| Typical UK retail price | £65 – £85 | £85 – £100 | £100 – £120 |
(Exact outputs and projections vary slightly by manufacturer—always check the BS EN 442 datasheet for your chosen brand.)
Why Upgrading to a Double Panel Often Saves Money on Installation
If a room feels cold or you are lowering your boiler flow temperature to 55°C (or switching to a heat pump), you have two ways to increase radiator output:
- Fit a wider single-panel radiator: Going from a 1000 mm wide Type 11 to a 1600 mm wide Type 11 requires moving furniture, repositioning at least one floorboard pipe, and making good the wall.
- Swap to a double-panel radiator of the same width: A 1000 mm wide Type 22 fits the exact same horizontal footprint, avoids eating into wall space, and usually costs only £25 to £40 more than the single-panel unit.
One plumbing check before swapping: Because a Type 22 is ~38 mm deeper than a Type 11, its valve centres sit slightly further out from the wall. If your radiator pipes come straight up through a concrete floor with zero play, a plumber may need angled fittings or a minor pipe offset; on suspended timber floors, copper or plastic pipes usually have enough flex to align cleanly.
Do Double-Panel Radiators Cost More to Run?
No. A common myth is that double-panel radiators "use twice as much gas" because they hold more water.
In reality, your home's heating bill is determined by how much heat escapes through your walls, roof, and windows—not the size of your radiators. Fitted with a thermostatic radiator valve (TRV), a double-panel radiator heats the room up faster and lets you turn your boiler's heating flow temperature down (from 70°C to 55°C–60°C), which keeps a modern condensing boiler in its most efficient condensing mode and can actually lower your gas bill.
When to Choose Single vs Double Panel
- Choose a single panel (Type 11) if: You are heating a small box bedroom, downstairs WC, utility room, or narrow hallway where the room's heat loss is low (under ~800 W) and keeping the wall profile slim is the priority.
- Choose a slim double (Type 21) if: You have a tight walkway or behind-the-door clearance, but a single panel falls 20%–40% short of the room's required BTU/hr.
- Choose a double panel (Type 22) if: You are heating a living room, kitchen, master bedroom, bay-window room, or any room in a property running a condensing boiler at low flow temperatures or planning for a heat pump.
Next Step: Match Your Wall Space to Your Room's Required Output
Before ordering, check the exact wattage your room needs—especially if you want to run your heating at a lower, more efficient water temperature.
Find the output your wall space needs with our Radiator BTU Calculator—enter your room dimensions and test outputs at your chosen water temperature.
Ready to shop? Compare single-panel (Type 11) and double-panel (Type 21/22) models of the same height and width at a UK radiator retailer once you have your target wattage.