Type 21 vs Type 22 Radiators: Compare Depth and Heat Output

A Type 22 radiator produces roughly 28% to 30% more heat than a Type 21 radiator of the exact same height and width, while projecting only 23 mm further from the wall and costing around £15 to £25 more to buy.

Both are double-panel steel convector radiators, so they look almost identical from the front. The difference sits hidden between the two water-filled panels:

Unless you are fitting a radiator in a narrow hallway, tight landing, or behind a door that cannot afford an extra 23 mm of projection, Type 22 is usually the better buy—especially if you run your boiler at a lower flow temperature or plan to switch to a heat pump later.

Side-by-Side Comparison: Standard 600 × 1000 mm Radiator

Most UK guides describe Type 21 as "slimmer" and Type 22 as "bulkier" without giving real measurements. Using BS EN 442 certified figures for a standard UK 600 mm high × 1000 mm wide compact steel radiator (Stelrad Softline Compact), here is what actually changes:

Specification (600 × 1000 mm) Type 21 (P+) Type 22 (K2) Difference
Panels / convector fins 2 panels / 1 fin row 2 panels / 2 fin rows +1 fin row
Radiator depth 77 mm 100 mm +23 mm
Total wall projection (incl. brackets) ~101 mm ~124 mm +23 mm
Heat output at ΔT50 (75°C flow / 65°C return) 1,345 W (4,589 BTU/hr) 1,732 W (5,910 BTU/hr) +29% heat
Heat output at ΔT30 (55°C flow / 45°C return) ~686 W (~2,340 BTU/hr) ~883 W (~3,014 BTU/hr) +29% heat
Typical UK retail price £85 – £100 £100 – £120 +£15 – £25

(Exact outputs and bracket projections vary slightly by manufacturer—always check the product's BS EN 442 datasheet before ordering.)

Why Wall Projection Matters More Than Radiator Depth

When measuring for a tight corridor or behind a doorway, do not look at the radiator's thickness alone. Wall brackets add roughly 24 mm behind the back panel, meaning:

Pipework watch-out when upgrading: If you are replacing an old Type 11 (single panel) or Type 21 with a deeper Type 22, the pipe centres sit further out from the wall. On copper pipes coming straight up through floorboards, a plumber may need to slightly offset the pipework or lift a board to prevent stressing the valve joints.

Why Type 22 Pays Off at Lower Flow Temperatures

Standard UK radiator outputs are advertised at ΔT50 (water entering at 75°C, leaving at 65°C, in a 20°C room). In reality, modern condensing boilers work far more efficiently with flow temperatures set to 55°C–60°C, and air source heat pumps typically run at 40°C–50°C.

At a 55°C flow temperature (ΔT30), every radiator loses nearly half its advertised output. Choosing a Type 22 instead of a Type 21 gives you almost 200 extra watts of real-world heat from the exact same wall footprint—allowing your boiler to condense properly without needing a wider radiator.

When to Choose Type 21 vs Type 22

Next Step: Check Your Room's Required Output First

Do not guess between Type 21 and Type 22 by room name alone. A well-insulated modern bedroom might only need 700 W, while a Victorian bedroom of the same floor area can need 1,500 W.