UK Air Source Heat Pump Sizing & Quote Checker
Start with your design heat loss. Compare it with the heat a proposed model delivers at the outdoor and water temperatures your installer plans to use.
Heat loss and quoted conditions
Use a heat-loss figure calculated for the outdoor temperature above. Estimate your whole-house heat loss
The built-in Vaillant figures are documented heating outputs at A−7/W35 in standard heating mode. A is outdoor air temperature and W is water flow temperature. Vaillant technical manual 0020330791_03, pp. 46–47
Capacity at your design point
0.4 kW surplus
- Design heat loss
- 5 kW
- Manufacturer-documented output
- 5.4 kW
- Outdoor / flow temperatures
- -7°C / 35°C
Use delivered space-heating kW for the exact model and operating mode. Ask the installer to confirm capacity at your design point, including the effects of defrost or quiet operation, and check radiator or floor output at the proposed water temperature.
Get Heat Pump QuotesGet Heat Pump Quotes
- Glow Green
- Quote link pending
- OVO
- Quote link pending
Frequently asked questions
Where do I get my design heat loss?
Use the peak space-heating load in kW from a room-by-room survey, or carry an estimate across from the whole-house heat loss calculator. Keep the outdoor design temperature with the figure.
Which kW figure should I take from the datasheet?
Find the delivered heating capacity for the quoted model at the matching outdoor air and leaving-water temperatures. A model name or nominal kW rating can refer to different test conditions.
Does meeting the design load tell me my annual running cost?
Annual energy use also depends on seasonal demand, water temperatures, performance and tariffs. Use the running cost calculator to compare bills.