BTU/hr to Watts Converter & Radiator Output Checker

Convert between watts and BTU/hr, then check a radiator’s catalogue rating against the heat your room needs at your chosen flow and return temperatures.

Convert a heat output

Enter the output printed on a radiator’s product sheet, or any heat output you want to convert.

Converted output

1,000 W

1 watt is approximately 3.412142 BTU per hour. Radiator listings often shorten BTU/hr to “BTU”.

Check this radiator in your room

The check uses the heat output above as the catalogue rating. Enter the temperatures you intend to run.

Calculate or save a room’s heat demand.

Output at your temperatures

515 W

About 1,756 BTU/hr at ΔT30. That is 51.5% of the catalogue output.

285 W short of the room heat demand.

Minimum catalogue output at ΔT501,555 W
How the radiator adjustment works

Operating ΔT is the average of the flow and return temperatures minus the room temperature. Multiply the rated output by (operating ΔT ÷ catalogue ΔT) raised to the power n.

The starting exponent of 1.3 is an estimate for a standard panel radiator. Use the model’s published exponent or output table when available. Zehnder’s radiator correction guide.

Compare radiator sizes

Look for at least 1,555 W at ΔT50. If space is tight, two radiators with a combined output at that rating can meet the same demand.

UK radiator retailer
Retailer link pending

Frequently asked questions

How many watts is 3,412 BTU/hr?

Approximately 1,000 watts, or 1 kW. Both watts and BTU per hour describe the rate at which a radiator gives out heat.

What does a ΔT50 catalogue rating mean?

The radiator was rated with its average water temperature 50°C above room temperature. For example, flow at 75°C and return at 65°C give a 70°C average, which is 50°C above a room at 20°C.

How do I check a radiator for lower flow temperatures?

Use the radiator’s catalogue rating and rated temperature difference. Enter the proposed flow, return and room temperatures, then compare the adjusted watts with the room heat loss. Use the manufacturer’s correction data for the exact model when available.